Generator Set Specifications
Genset Model | 260GFT - J1 |
Structure | integrated |
Exciting Method | AVR Brushless |
Rated Power ( kW/kVA ) | 260/325 |
Rated Current ( A ) | 468 |
Rated Voltage ( V ) | 230/400 |
Rated Frequency ( Hz ) | 50/60 |
Rated Power Factor | 0.8 LAG |
No Load Voltage Range | 95% ~ 105% |
Stable Voltage Regulation Rate | ≤±1% |
Instantaneous Voltage Regulation Rate | ≤-15% ~ +20% |
Voltage Recover Time | ≤3 S |
Voltage Fluctuation Rate | ≤±0.5% |
Instantaneous Frequency Regulation Rate | ≤±10% |
Frequency Stabilization Time | ≤5 S |
Line-voltage Waveform Sinusoidal Distortion Rate | ≤2.5% |
Overall Dimension ( L*W*H ) ( mm ) | 3250*1550*1950 |
Net Weight ( kg ) | 2680 |
Noise dB ( A ) | <93 |
Overhaul Cycle ( h ) | 25000 |
Engine Specifications
Model | NY196D28TL ( AVL Technology ) |
Type | Inline, 4 strokes, electric control ignition, pre-mixed and turbocharged inter-cooled lean burn. |
Cylinder Number | 6 |
Bore*Stroke ( mm ) | 152*180 |
Total Displacement ( L ) | 19.597 |
Rated Power ( kW ) | 280 |
Rated Speed ( r/min ) | 1500/1800 |
Fuel Type | Biomass gas |
Control Panel
Model | 260KZY, NPT brand |
Display Type | Multi-function LCD display |
Control Module | HGM9320 or HGM9510, Smartgen brand |
Operation Language | English |
Alternator
Model | XN4E |
Brand | XN ( Xingnuo ) |
Shaft | Single bearing |
Rated Power ( kW/kVA ) | 260/325 |
Enclosure Protection | IP23 |
Efficiency ( % ) | 93.2 |
Main Uses
(1) The unit using gas-fired boiler can mix with natural gas or pipeline gas under the condition that the original boiler equipment is basically unchanged, so as to greatly reduce the consumption of natural gas or pipeline gas and reduce the cost of gas.
(2) In the living quarters using natural gas, pipeline gas and ordinary biogas, they can be connected to the grid to supply gas to families, reduce the cost of gas, and increase the profit of gas sales significantly with the same retail price of gas.
(3) The biological natural gas produced by this equipment is used to drive the internal combustion engine for power generation. The power generation capacity is 20-1000KW / h. if it is less than or greater than this range, it can be specially designed for users.