Generator Set Specifications
Genset Model | 500GFT |
Structure | integrated |
Exciting Method | AVR Brushless |
Rated Power ( kW/kVA ) | 500/625 |
Rated Current ( A ) | 900 |
Rated Voltage ( V ) | 230/400 |
Rated Frequency ( Hz ) | 50/60 |
Rated Power Factor | 0.8 LAG |
No Load Voltage Range | 95% ~ 105% |
Stable Voltage Regulation Rate | ≤±1% |
Instantaneous Voltage Regulation Rate | ≤-15% ~ +20% |
Voltage Recover Time | ≤3 S |
Voltage Fluctuation Rate | ≤±0.5% |
Instantaneous Frequency Regulation Rate | ≤±10% |
Frequency Stabilization Time | ≤5 S |
Line-voltage Waveform Sinusoidal Distortion Rate | ≤2.5% |
Overall Dimension ( L*W*H ) ( mm ) | 5400*2250*2540 |
Net Weight ( kg ) | 8400 |
Noise dB ( A ) | <93 |
Overhaul Cycle ( h ) | 25000 |
Engine Specifications
Model | NY396D55TL ( AVL Technology ) |
Type | Inline, 4 strokes, electric control ignition, turbocharged and intercooled, pre-mixed lean burn |
Cylinder Number | 6 |
Bore*Stroke ( mm ) | 200*210 |
Total Displacement ( L ) | 39.584 |
Rated Power ( kW ) | 550 |
Rated Speed ( r/min ) | 1500/1800 |
Fuel Type | Natural gas/ Biogas |
Oil (L) | 170 |
Control Panel
Model | 500KZY, NPT brand |
Display Type | Multi-function LCD display |
Control Module | HGM9320 or HGM9510, Smartgen brand |
Operation Language | English |
Alternator
Model | XN5FS |
Brand | XN ( Xingnuo ) |
Shaft | Single bearing |
Rated Power ( kW/kVA ) | 500/625 |
Enclosure Protection | IP23 |
Efficiency ( % ) | 94.6 |
Our Services
Lifetime
According to product design and end users' years experience, strictly following our operation manual and make gen-set load under 85% of prime power, we guarantee the major overhaul terminal more than 15000 hours, and lifetime is over 20 years.
After Service
12 months or 1500 running hours warranty covering all manufacturing defects (whichever comes first)since leaving China port, our company provides free easily-damaged parts for the faults caused by the quality of products or raw material, but exclude the damageable parts of engine due to customer's incorrect man-made operation. After expiration, our company provides spare parts with cost for maintenance forever.